|
Calculating and Using K-Factors
1. What is a K-factor
Simply stated a K-factor is a dividing factor. The term is usually encountered
when dealing with pulse signals although analog K-factors are sometimes
used.
2. Pulse Signal K-factors
All pulse output type flow meters when they are dispatched by their manufacturer
will have a calibration certificate. The calibration certificate will
show that the meter has been calibrated over its flow range and noted
on the certificate will be the average K-factor for the meter.
This K-factor will be given in terms of the number of
pulses produced by the meter for a given volumetric flow. (e.g.) 200 pulses
per U.S. gallon, 150 pulses per liter etc.
This K-factor is the value that is entered into a batch
meter or indicator/totalizer in order to give a readout in engineering
units.
Example 1
If the display on a rate meter is required in U.S. gallons per second,
and the K-factor of the flow meter is 210 pulses per U.S. gallon, then
the K-factor entered into the rate meter would be 210.
If a totalizer associated with the same flow meter was
to be set up so as to totalize in U.S. gallons the totalizer K-factor
would be 210.
If the totalizer was to be set to totalize in tenths
of a gallon the K-factor would be 210/10 = 21
Example 2
If the display on a rate meter is required in U.S. gallons per minute,
and the K-factor of the flow meter is 210 pulses per U.S. gallon, then
the K-factor entered into the rate meter would be: 210/60 = 3.5
3. K-factors for Analog Input Signals
When batching, indication or totalization has to be carried out using
an analog input signal a KEP product first converts the 4 to 20 mA signal
into a 0 to 10000 Hz. signal. The K-factor is then calculated by relating
the engineering unit equivalent of 20 mA to the 10000 Hz. signal.
Example 3
A vortex meter outputs 20 mA when the flow is 2000 U.S. gallons per minute,
we wish to display the rate in gallons per minute.
The rate K-factor is = 10000/2000 = 5
The value of the totalizer K-factor will depend on whether
the flow rate was given in units per second, minute or hour and whether
it is desired to totalize in whole units, tenths, hundredths etc.
If the flow rate was given in units per second
the totalizer K-factor (for whole units) is obtained by multiplying the
rate K-factor by 1.
If the flow rate was given in units per minute
the totalizer K-factor (for whole units) is obtained by multiplying the
rate K-factor by 60.
If the flow rate was given in units per hour the
totalizer K-factor (for whole units) is obtained by multiplying the rate
K-factor by 3600.
The totalizer K-factor in example 3 will be =
5 x 60 = 300 in order to totalize in gallons.
If we wished to totalize in tenths of a gallon the K-factor
would be 5 x 60/10 = 30
Example 4
An electromagnetic flow meter outputs 20 mA when the flow is 20 liters
per second, we wish to display the flow rate in liters per second and
totalize in M³.
The rate K-factor is 10000/20 = 500
The totalizer K-factor will be 500 x 1/0.001 = 500000
4. Multi-Point K-factors
Some flow applications dictate that multiple K-factors are used. Two applications
that require multiple K-factors are:
- flow meters with non linear outputs
- wide turndown flow applications
KEP meters have an option available that allows the user
to input from 3 to 16 K-factors. This multi-point K-factor option is available
for both pulse and analog inputs.
5. Multi-Point K-factors for Pulse inputs
The first step is to calculate K-factors to cover each flow range. This
is done by taking the information on the flow meter manufacturer's calibration
sheet and calculating the K-factors as per section 2. An alternative to
using the manufacturers' data is to conduct tests on site against a calibrated
standard.
The second step is to relate an incoming frequency range
from the flow meter to a given calculated K-factor.
The final step is to program these values into the KEP
instrument.
Example 5
A turbine flow meter has the following calibration data.
| % Flow |
Flow Rate (gpm) |
Total Pulses |
Frequency (Hz) |
Pulses Per Gallon |
K-factor (ppg) |
| 0 |
0 |
0 |
0 |
0 |
0 |
| 20 |
10 |
510 |
8.5 |
51 |
51 |
| 40 |
20 |
1025 |
17.08 |
51.25 |
51.25 |
| 60 |
30 |
1550 |
25.83 |
51.667 |
51.667 |
| 80 |
40 |
2080 |
34.67 |
52 |
52 |
| 100 |
50 |
2620 |
43.67 |
52.4 |
52.4 |
From the above calibration sheet data we can relate the
incoming frequency to the K-factor as follows.
| Input Frequency (HZ) |
K-factor |
| 0 |
51 |
| 8.5 |
51 |
| 17.08 |
51.25 |
| 25.83 |
51.667 |
| 34.67 |
52 |
| 43.67 |
52.4 |
The 16 point K-factor would be programmed as follows.
| Display Prompt |
Value to Enter |
Comments |
| Enter Point |
|
enter frequency value for point 1 |
| Freq01? |
0 |
|
| Freq01? 0.0000 |
|
enter K-factor to be used for |
| K Factor01? |
51 |
frequencies 0 to 8.5 Hz |
| Enter Point |
|
enter frequency value for point 2 |
| Freq02? |
8.5 |
|
| Freq02? 8.5000 |
|
enter K-factor to be used for |
| K Factor02? |
51 |
frequencies 8.5 to 17.08 Hz |
| Enter Point |
|
enter frequency value for point 3 |
| Freq03? |
17.08 |
|
| Freq03? 17.08 00 |
|
enter K-factor to be used for |
| K Factor03? |
51.25 |
frequencies 17.08 to 25.83 Hz |
| Enter Point |
|
enter frequency value for point 4 |
| Freq04? |
25.83 |
|
| Freq04? 25.83 00 |
|
enter K-factor to be used for |
| K Factor04? |
51.667 |
frequencies 25.83 to 34.67 Hz |
| Enter Point |
|
enter frequency value for point 5 |
| Freq05? |
34.67 |
|
| Freq05? 34.6700 |
|
enter K-factor to be used for |
| K Factor05? |
52 |
frequencies 34.67 to 43.67 Hz |
| Enter Point |
|
enter frequency value for point 6 |
| Freq06? |
43.67 |
|
| Freq06? 43.6700 |
|
enter K-factor to be used for |
| K Factor06? |
52.4 |
frequencies from 43.67 Hz onwards |
| Enter Point |
|
enter frequency value for point 7 |
| Freq07? |
43.67 |
|
| Freq07? 43.6700 |
|
enter K-factor to be used for |
| K Factor07? |
52.4 |
frequencies from 43.67 Hz onwards |
Note that because the K-factor for the last two points are the same, any
frequency higher than 43.67 Hz will be modified by a K-factor of 52.4
The set up is now complete.
6. Multi Point K-factors for Analog Inputs
The procedure for analog inputs is essentially the same as for pulse inputs.
The first step is to calculate K-factors to cover each
flow range. This is done by taking the information on the flow meter manufacturer's
calibration sheet and calculating the K-factors as per section 3. An alternative
to using the manufacturer's data is to conduct tests on site against a
calibrated standard.
The second step is to relate an incoming flow value from
the flow meter to a given calculated K-factor.
The final step is to program these values into the KEP
instrument.
Example 6
A vortex flow meter has the following calibration data.
Base K-factor 10000/100 = 100
| Output (mA) |
True Flow Rate (gpm) |
Indicated Flow Rate (gpm) |
Ratio (Actual:True) |
K-Factor (base x ratio) |
| 4 |
0 |
0 |
1 |
100 |
| 8 |
25 |
25 |
1 |
100 |
| 12 |
50 |
51 |
1.02 |
102 |
| 16 |
75 |
78 |
1.04 |
104 |
| 20 |
100 |
105 |
1.05 |
105 |
Using the MASStrol as an example the K-factors would
be programmed as follows.
| Display Prompt |
Value to Enter |
Comments |
| Enter Point |
|
enter flow |
| Actual01? |
0 |
value for point 1 |
| Actual01? 0.0000 |
|
enter K-factor to be used |
| K Factor01? |
100 |
for flows 0 to 25 gpm |
| Enter Point |
|
enter flow |
| Actual02? |
25 |
value for point 2 |
| Actual02? 25.0000 |
|
enter K-factor to be |
| K Factor02? |
100 |
used for flows 25 to 50 gpm |
| Enter Point |
|
enter flow |
| Actual03? |
50 |
value for point 3 |
| Actual03? 50.0000 |
|
enter K-factor to be |
| K Factor03? |
102 |
used for flows 50 to 75 gpm |
| Enter Point |
|
enter flow |
| Actual04? |
75 |
value for point 4 |
| Actual04? 75.0000 |
|
enter K-factor to be |
| K Factor04? |
104 |
used for flows 75 to 100 gpm |
| Enter Point |
|
enter flow |
| Actual05? |
1000 |
value for point 5 |
| Actual05? 50.0000 |
|
enter K-factor to be |
| K Factor03? |
104 |
used for flows 100 to 1000 gpm |
Note that the point after the final one should have a flow
value entered that is very much higher than the true maximum flow rate
of the meter. Note also that as the last two K-factors are the same any
flow above 100 gpm will be modified by a K-factor of 104. The setup is
now complete.
|